Power Pack with Battery Back Up
Technical Specifications
Input voltage | : 110 V. or 230 AC (1 Phase) |
: or 110 V. or 415 V. AC (3 Phase) | |
Out put | : 24 V, 30 V, 110 V DC (+/- 25 % from No load to full load) |
Output Load Stored | : 50 or 100 Wsec. |
Output Load Non Stores | : 50 or 100 Watt |
Mounting | : Base Mounting |
Description
Function:
Power pack is used as a power source for VCB panels in substations where station battery supply is not available. Power pack stores the energy in built in Batter. Aux. supply is taken from PT. and the stored energy cab be used to Trip / Close the Circuit breakers when AC input is not available.
There are total two output. One output is for stored energy and other is for non-stored. Stored output can be used when AC input is not available. Non- stored output will be available as long as AC input is present.